CFP Standard Conventional Fire Alarm Panel (2, 4 and 8 zone)

£0.00 inc. VAT

CFP Standard Conventional Fire Alarm Panel (2, 4 and 8 zone)

Description

CFP Standard Conventional Fire Alarm Panel (2, 4 and 8 zone)

 

User Manual  Download User Manual

 

LPCB certified to EN54-2/4, C-TEC’s CFP conventional fire alarm panel offers an array of user and installer-friendly features at a very competitive price.

 

Supplied in an attractive flush or surface mountable plastic enclosure, it includes two detector zones, four conventional sounder circuits, class change and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry.

 

A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive test and fault finding facilities are also provided.

Optional repeaters, relay expansion boards and EN54-13 system compliance devices are also available.

 

More Information:

  • Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13. compliance from the BSI.
  • Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
  • Manufactured by C-TEC in the UK.
  • Two detector zone circuits.
  • Four conventional sounder circuits*
  • Integral 1.5A EN54-4/A2 compliant switch mode PSU.
  • Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
  • Two on-board relays (Fire and Fault).
  • Two open-collector outputs (Remote and Reset).
  • ‘Class change’ and alert inputs.
  • Installer-friendly design.
  • Attractive flush or surface mountable plastic lid and enclosure – no bezel required.
  • Low 25mA quiescent current.
  • Multiple indicators.
  • System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards and optional EN54-13 compliant sounder circuit boards.
  • Space for two x 12V 3.3Ah VRLA batteries.
  • Fully compatible with C-TEC’s ActiV range of conventional fire detectors.

 

Technical Specifications:

  • Approvals/certifications Certified to EN54-2/4 by the LPCB (176b) / (0832-CPD-1704).
  • Mains supply 230V 50/60Hz.
  • Mains rated current 350mA maximum.
  • Internal power supply 19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
  • Total output current limited to 1.5A @ 230Vac (ImaxA eq 146mA).
  • Quiescent current 25mA (mains failed, internal sounder active, PSU & gen fault LED lit).
  • Max battery size and type 2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
  • No. of detector zone circuits 2, 4, 8 (Max. length per circuit is 500m).
  • Call point resistor value: 470 to 680Ω.
  • Max. devices per detector zone: 25 detectors (or 32 detectors/manual call points combined).
  • No. of conventional sounder circuits: 4 (Max. length per circuit is 500m).
  • EOL resistor value: 6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
  • Alarm voltage: 27V max, 20V min (final battery voltage).
  • Max. sounder output current: 4 x 200mA (800mA total).
  • Auxiliary relays Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
  • Open collector outputs Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc)
  • Other outputs: 24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault removed).
  • Auxiliary inputs Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger, Max. input voltage 27V (non-latching)
  • Engineer (AL3) functions: Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones for non-latching operation; Program sounders to resound (or not resound) when a new zone enters alarm; Enter fault diagnostic facilities
  • Expansion connections: Yes – for optional network driver cards (one required per repeater system), relay output cards and EN54-13 sounder circuit interface boards.
  • Product dimensions (mm): 380 W x 235 H x D 96mm.
  • Hole required for flush mounting: 367 W x 220 H x 75 D mm. No bezel required.
  • Construction & finish: Plastic lid and base; RAL7035 textured.
  • IP Rating: IP30.
  • Weight: 1.75kg (without batteries).
  • Operating conditions/temperature: -5ºC to +40ºC. Max relative humidity: 95%.

Additional information

Number of Zones:

2 Zone, 4 Zone, 8 Zone